Home News About Contact Sitemap  
   

Installing and Wiring
Low Voltage Lighting Controls

Relay Panels

Relays are installed in a relay panel. Douglas panels for 6, 12, 24, 36, 48 and 72 relay capacity are available. Size the panel to allow for future expansion.

Install the required amount of relays and add when necessary. Douglas LitePak panels (8 relays, expandable to 16 relays with an Expansion Pak) are designed for small projects.


Panel Location

The load (lighting or other) must be connected to the relay.

In most cases, it is best to locate the relay panel adjacent to the circuit breaker panel.

In some cases, though, there is less wiring if a small panel is located nearer to the load. This can occur where several rooms share the same circuit breaker.

installing low voltage control


Panel Wiring -Line Voltage

Relay panels have a line voltage compartment for the lighting loads and a low voltage compartment for the relay controls. Install conduit to panels at the appropriate locations.

The line voltage compartment can be partitioned to support different voltages or voltage sources. In the diagram above, a partition exists for 120V and 277V sections.

Connect from the breaker to the relay and then to the load. In some cases, one circuit breaker services several switched loads. If so, parallel the breaker wire feed to several relays and then run the individual switch legs to the loads.

Neutral wires are routed back to the breaker panel and connect to the neutral terminals.


Low Voltage Controls -Panel Wire Types

Low voltage lighting control wiring for relays, switches and transformers is class 2 rated, 18 AWG. Solid wire is recommended as it is easier to terminate and there are no strands that could cause shorts.

For panels that are digitally networked, conductors rated for data signal connection are required. Refer to the product specifications for data wire types.


Low Voltage Controls -Panel Wiring Strategy

Relays only require power when they are switched. Switching a relay requires only one electrical sine wave (17 milliseconds). Thus, one control transformer can be used for many relays.

When relays are switched as a group by a relay scanner device, the scanner sequences the relays ON or OFF. Thus, only the relays connected to one scanner output are switched at any given moment.

In most cases a relay panel only has one transformer. A common wire is supplied to all of the remote switches and each switch has a control wire that connects to the appropriate relay or scanner input.

If there are several panels interconnected and wire distances are less than 500 feet (150 meters) it may prove practical to use one transformer for all of the panels. In larger projects, each panel usually has its own transformer. Local switches use this transformer to switch the relays.

If a relay scanner is installed in the panel, the scanner also uses the panel’s transformer to switch the relays. The scanner’s switch inputs are an isolated circuit. This permits a transformer located elsewhere to be used to switch the inputs of all scanners in all panels, permitting a building-wide control scheme.


Wire Distance from Panels

Allowable wire distances from the relay to the 2-wire switch that controls it are shown in the following list.

wiring low voltage control

1.5 A & 3.0A RATED SWITCHES
applies to all Douglas 2-wire wall switches, sensors and relay control devices

1 relay/switch: 2000'/600m wire length
2 relays/sw: 1500'/450m wire length
3 relays/sw: 1000'/300m wire length
4 relays/sw: 500'/150m wire length


3.0A RATED SWITCHES
applies to Douglas WR-8001, WRK-8001 and élan 2-wire switches only

6 relays/sw: 300'/90m wire length
8 relays/sw: 150'/50m wire length